Electrical Buying Guide

How to Select Industrial Switchgear — A Procurement Buying Guide

Switchgear is specified by two ratings, not one. The current rating decides what the device carries; the breaking capacity decides whether it can safely interrupt a fault. Getting the second wrong is a safety failure, not a performance one.

Last updated
Reading time
7 minutes
Written by
AMZ Industries

MCB, MCCB or ACB

The three families cover ascending current ranges and ascending levels of adjustability. As the rating rises, protection settings move from fixed to fully adjustable, because larger installations need discrimination between devices in series.

DeviceTypical rangeAdjustabilityUsual position
MCBLow current final circuitsFixed characteristicFinal distribution boards
MCCBModerate to high currentAdjustable thermal, often adjustable magneticSub-main distribution, motor feeders
ACBHigh current main incomersFully adjustable electronic trip unitMain incoming and bus-section duty

Breaking capacity is the safety rating

Breaking capacity is the maximum prospective fault current the device can interrupt safely. It must equal or exceed the fault level available at its point in the installation, which is determined by the supply transformer and the impedance of the cabling between it and the device.

A breaker rated correctly for load current but below the available fault level may fail catastrophically during a short circuit rather than clearing it. This is why fault level at each board has to be established during design rather than assumed, and why a like-for-like replacement should never be downgraded on breaking capacity to save cost.

Tripping curves

A tripping curve defines how quickly the magnetic element operates relative to the rated current. The right curve lets a circuit start normally without nuisance tripping while still clearing genuine faults quickly.

  • B curve — trips at a low multiple of rated current; suits resistive loads and long cable runs with low fault current
  • C curve — the general-purpose choice for mixed loads with moderate inrush
  • D curve — tolerates high inrush; used for transformers, motors and other highly inductive loads
  • K and Z curves — specialist characteristics for motor circuits and sensitive electronic equipment respectively

Contactors and overload relays

A contactor switches a load repeatedly under normal operation; a breaker protects it against faults. They are complementary, not alternatives. Contactors are selected on utilisation category — the same contactor carries a lower rating switching a motor than switching a resistive load, because motor starting current and the arc energy at break are far higher.

  • AC-1 covers resistive and lightly inductive loads
  • AC-3 covers squirrel-cage motor starting and switching while running — the common motor case
  • AC-4 covers inching, plugging and reverse braking, which is far more severe duty
  • Overload relays protect the motor thermally and must be set to the motor full-load current, not the contactor rating

Discrimination and coordination

In a correctly coordinated installation, a fault on a final circuit operates only that circuit’s device, leaving upstream boards live. Achieving that requires the upstream device to be slower and higher-rated than the downstream one across the whole fault range — which is why adjustable trip units matter at the larger sizes.

What to include in a switchgear enquiry

  • Device type, current rating and number of poles
  • Required breaking capacity, based on the fault level at that point
  • Tripping curve or trip unit settings required
  • System voltage and frequency
  • Enclosure requirement and ingress protection rating
  • Accessories — auxiliary contacts, shunt trips, undervoltage releases, motor operators
  • Brand preference, quantity, delivery city and required date

Switchgear FAQs

Switchgear — Frequently asked questions

Quick answers on sourcing, specifications and quotations.

Still have a question? Talk to our team
What is the difference between an MCB, an MCCB and an ACB?

They cover ascending current ranges with ascending adjustability. MCBs protect low-current final circuits with a fixed characteristic. MCCBs cover higher currents with adjustable thermal and often adjustable magnetic settings. ACBs are used on high-current main incomers with fully adjustable electronic trip units.

What is breaking capacity and why does it matter?

Breaking capacity is the maximum prospective fault current the device can interrupt safely. It must meet or exceed the fault level at that point in the installation. A device below the available fault level can fail destructively during a short circuit instead of clearing it.

Which tripping curve should I use for a motor circuit?

A D curve, or a purpose-designed motor protection characteristic. Motor starting current is several times full-load current, and a B or C curve will nuisance-trip on every start.

Do contactors replace circuit breakers?

No. A contactor is a switching device for routine operation; a breaker is a protective device for fault conditions. A motor starter normally uses both, with an overload relay set to the motor full-load current.

Request a Quote

Need to source switchgear?

Tell us the grade, quantity and delivery city for your Switchgear requirement. Our team responds with availability, pricing and lead time — in a single response.

We serve clients across Lahore, Karachi, Faisalabad, Multan, Sialkot, Hyderabad, and all major industrial zones in Pakistan.