Electrical Buying Guide

How to Specify Industrial Cables — A Procurement Buying Guide

Cable is sized for three things at once — current capacity, voltage drop and fault withstand — and the largest of the three governs. Choosing on current alone is the most common reason a correctly rated cable still fails to perform.

Last updated
Reading time
7 minutes
Written by
AMZ Industries

The three sizing criteria

A cable must carry the load current continuously without exceeding its insulation temperature, deliver acceptable voltage at the far end, and survive the prospective fault current for as long as the protective device takes to clear. Each criterion produces a minimum conductor size, and the cable you buy has to satisfy the largest of them.

  • Current-carrying capacity — the base rating, before derating is applied
  • Voltage drop — usually the governing criterion on long runs, where a cable rated comfortably for current still delivers too little voltage at the load
  • Fault withstand — the conductor must not be damaged by the let-through energy before the breaker or fuse operates

Derating — where published ratings stop applying

Published current ratings assume reference installation conditions. Real installations rarely match them, and the applicable derating factors multiply together, so several modest factors combine into a substantial reduction.

  • Ambient temperature above the reference value reduces capacity — significant in Pakistani summer conditions
  • Grouping cables together in a tray or conduit reduces each cable’s rating
  • Buried cables depend on soil thermal resistivity and depth of laying
  • Enclosure in conduit or trunking restricts heat dissipation compared with free air

Insulation and sheath materials

Insulation sets the conductor operating temperature and therefore the current rating; the outer sheath protects against the external environment.

MaterialCharacteristicTypical use
PVCLower operating temperature, economicalGeneral indoor power and control wiring
XLPEHigher operating temperature and current ratingPower distribution, main feeders
LSZHLow smoke, zero halogen when burningEnclosed and occupied areas where smoke toxicity matters
Rubber / EPRVery flexible, tolerant of movementTrailing cables, portable and mobile equipment
PTFE and high-temperatureWithstands elevated ambient temperatureFurnaces, hot process areas

Armouring and mechanical protection

Armour protects the cable from mechanical damage and can serve as an earth path. Steel wire armour is the general standard for buried and industrial power cables; aluminium wire armour is used on single-core AC circuits to avoid the circulating currents that steel would induce.

Control, instrumentation and screening

Control cables carry switching signals and are specified largely on core count and flexibility. Instrumentation cables carry low-level analogue and data signals and are far more sensitive to electrical noise — which is what screening addresses.

  • Individually screened pairs prevent crosstalk between signals within the same cable
  • Overall screening protects the whole bundle from external interference
  • Both individual and overall screening is specified where signal integrity is critical
  • Earth the screen at one end only unless the system design specifies otherwise — earthing both ends can create a circulating current
  • Route instrumentation cable away from power cable, and cross at right angles where crossing is unavoidable

Voltage grade and glanding

Cable voltage grade is expressed as two figures — the phase-to-earth and phase-to-phase voltages the insulation is designed for. The cable grade must equal or exceed the system voltage. Terminating hardware matters too: the gland must suit the cable construction and the enclosure’s ingress protection rating, and armoured cable needs a gland that terminates the armour correctly for earth continuity.

What to include in a cable enquiry

  • Number of cores and conductor cross-sectional area
  • Conductor material — copper or aluminium
  • Insulation and sheath material, and voltage grade
  • Armoured or unarmoured, and screening requirement for control and instrumentation
  • Installation method — buried, tray, conduit, free air — and ambient temperature
  • Total length required per drum, plus glands and accessories
  • Delivery city and required date

Industrial Cables FAQs

Industrial Cables — Frequently asked questions

Quick answers on sourcing, specifications and quotations.

Still have a question? Talk to our team
How do I size an industrial cable?

Size it against three criteria — current-carrying capacity after derating, voltage drop over the run length, and fault withstand for the clearing time of the protective device. Each gives a minimum size, and the largest governs. On long runs voltage drop usually decides.

What is the difference between XLPE and PVC cable?

XLPE insulation operates at a higher conductor temperature than PVC, so an XLPE cable of the same size carries more current. XLPE is standard for power distribution; PVC remains common for general indoor power and control wiring.

When is armoured cable required?

Where the cable faces mechanical damage — buried runs, industrial floor level, and areas with vehicle or plant movement. Steel wire armour is the general standard, though single-core AC circuits use aluminium wire armour to avoid circulating currents.

Should a cable screen be earthed at one end or both?

For instrumentation signals, earth the screen at one end only unless the system design states otherwise. Earthing both ends can create a circulating current in the screen that injects the very noise the screen was fitted to exclude.