Electrical Buying Guide

How to Select Industrial Control Components — A Procurement Buying Guide

Control system components have to work together, and the point they most often fail to is the signal interface. Getting I/O types, signal standards and voltage levels agreed before ordering prevents most integration problems.

Last updated
Reading time
7 minutes
Written by
AMZ Industries

Sizing a PLC

A PLC is specified by its input and output count and type, its processing and memory capability, and the communication protocols it must speak. Count the I/O the application needs, then add spare capacity — expansion is normal, and a controller with no free I/O forces a hardware change for a small process modification.

  • Digital inputs and outputs for switches, sensors, valves and contactors
  • Analogue inputs and outputs for transmitters, control valves and drive references
  • Specialist modules for thermocouples, RTDs, high-speed counting and motion
  • Communication protocols must match the drives, instruments and any supervisory system already on site

Signal standards

The 4–20 mA current loop remains the industrial standard for analogue signals, and for a good reason: current is unaffected by voltage drop over long cable runs, and the live zero at 4 mA distinguishes a genuine zero reading from a broken wire. Voltage signals are simpler but are susceptible to drop and interference over distance.

SignalCharacteristicTypical use
4–20 mAImmune to voltage drop; live zero detects wire breakProcess transmitters over long runs
0–10 VSimple, but degrades over distanceShort in-panel connections, some drive references
Digital 24 V DCThe industrial standard for discrete signallingSwitches, proximity sensors, valve feedback
Fieldbus and industrial EthernetMultiple devices on one cable, with diagnosticsDistributed I/O, drives, instruments

Sensors and detection

Sensor choice follows the target material, the sensing distance, the environment and the required switching speed.

  • Inductive proximity sensors detect metal only, at short range, and are extremely robust
  • Capacitive sensors detect non-metallic materials and suit level detection through a vessel wall
  • Photoelectric sensors cover longer ranges; through-beam is the most reliable, diffuse the simplest to install
  • Ultrasonic sensors suit level measurement and targets that reflect light poorly
  • Confirm output type — PNP or NPN, normally open or normally closed — against the PLC input card

Variable frequency drives

A VFD is sized on motor current rather than on motor power alone, and on the load type. A variable torque load such as a fan or centrifugal pump is far less demanding than a constant torque load such as a conveyor or positive displacement pump, which needs full torque at low speed.

  • Match the drive rating to motor full-load current, and confirm the load type
  • Confirm whether the motor is suitable for inverter operation
  • Include braking resistors where a high-inertia load must decelerate quickly
  • Specify EMC filtering, and use screened motor cable with the screen terminated correctly at both ends
  • Account for enclosure heat — drives dissipate significant heat inside a panel

Panel devices and terminals

Pushbuttons, selector switches, indicator lamps and terminal blocks are individually inexpensive and collectively determine how workable the panel is. Standardise on one terminal system and one device range rather than mixing, so spares are simple and wiring is consistent.

  • Confirm panel cut-out diameter for operator devices, and the IP rating on the front face
  • Emergency stop devices must be the correct latching, twist-release type and wired to the safety system, not to the PLC alone
  • Terminal blocks should suit the conductor size, with disconnect terminals where isolation for testing is needed
  • Fused terminals protect individual instrument circuits without tripping a whole group

What to include in a control components enquiry

  • I/O count by type, with the spare capacity required
  • Communication protocols in use on site
  • Signal types and voltage levels for each interface
  • Sensor targets, ranges, environment and required output type
  • Motor data and load type for any drives
  • Panel device requirements and IP rating
  • Preferred manufacturer where the site standardises on one, quantity and delivery city

Industrial Control Components FAQs

Industrial Control Components — Frequently asked questions

Quick answers on sourcing, specifications and quotations.

Still have a question? Talk to our team
Why is 4–20 mA still the standard analogue signal?

Because current is unaffected by voltage drop along a long cable run, and because the live zero at 4 mA distinguishes a genuine zero measurement from a broken wire or failed transmitter. A 0 V reading on a voltage signal is ambiguous.

How do I size a variable frequency drive?

Size it on motor full-load current rather than nominal power, and confirm the load type. Variable torque loads such as fans and centrifugal pumps are far less demanding than constant torque loads such as conveyors, which need full torque at low speed.

What is the difference between PNP and NPN sensor outputs?

They describe which side of the supply the sensor switches. PNP switches the positive line to the input, NPN switches the negative. The sensor output type must match the PLC input card configuration or the signal will not be read.

How much spare PLC I/O should I allow?

Enough that foreseeable process changes do not require new hardware. Spare I/O specified at the outset costs a fraction of adding a module and re-terminating a panel later.